Megger BITE 2P Battery Impedance Tester with Built-In Printer (246004)
The Megger 246004 BITE 2P is a portable battery impedance tester that checks the condition of lead acid and nickel cadmium cells up to 7,000 Ah with the string still online. It is the upgraded version of the Megger 246004 BITE 2P with the same data logging feature set plus a built in printer for on site hard copy records. It suits maintenance teams responsible for standby and backup battery systems in telecoms, utilities, data centers, hospitals, aircraft, and military installations.
Key Features Megger 246004 BITE 2P
- Online testing: applies a test current across the battery string while it stays on line then measures the voltage drop of each cell or jar and calculates impedance with no battery discharge and no stress on the battery
- Fast testing: under 20 seconds per cell and intercell connector so one person can test a string quickly
- Complete string assessment: measures internal cell impedance DC voltage, and intercell (strap) resistance covering the electrical path from terminal plate to terminal plate
- Built in thermal printer: 110 mm (4.25 in.) print width to review the active test and leave a printed record at the site
- Data logging: the receiver stores readings in internal memory and data can be downloaded to a PC for analysis including with Megger PowerDB software
- On-board pass, warning, and fail indications: quick feedback on each cell as you go
- Accuracy: AC impedance ±5% + 1 LSD, and DC voltage ±(1.5% of reading + 1 LSD)
- Impedance range: 0 to 100 mΩ across three ranges with resolution down to 1 µΩ
- Source current: 10 A nominal at 50/60 Hz, with a maximum battery string test voltage of 275 V DC (larger strings can be sectioned)
- Rechargeable receiver: NiMH battery pack giving about 5 hours of continuous use
- All-in-one carrying case: the transmitter case also holds the standard accessories and some optional ones
- Dual-voltage supply: 110/230 V AC 50/60 Hz
Typical Applications
- Telecom and data center standby battery maintenance
- Power utility, substation, and generating station battery banks
- Medical, industrial, commercial, aircraft, and military battery systems
- Trending impedance over time with Megger recommending semiannual readings for flooded batteries and quarterly for VRLA
- Identifying weak cells high resistance connections and failing jars before they cause an outage
Why Choose It
Regular impedance testing is a practical alternative to load testing which needs downtime and repeated discharges. The Megger 246004 BITE 2P tests the whole string online in minutes prints results at the site and stores readings for trending helping you replace cells at the right time.